APPLICATION NOTE · T8-DSA-604
The module compares eight channels with source-reported environmental, building, boundary, construction, workplace and NR criteria, displaying margins and spectral overlays. Its current-frame comparisons help locate noise sources. A formal result requires the applicable standard edition, measurement locations, averaging period and corrections. Occupational assessment additionally requires representative task durations and a duration-normalized exposure calculation; an instantaneous comparison cannot establish an eight-hour result.
NR comparison uses the unweighted octave-band spectrum and the chosen curve. For total A-weighted criteria, the source describes a comparison at every refresh. Treat those values as current-frame indications until the complete measurement and time-averaging requirements of the selected method have been met.
NR evaluation is particularly laborious: the NR curves are a family of curves that bend with frequency, and the measured octave spectrum must be compared with the family band by band. The module automates this. With the standard and period selected, every refresh calculates and judges all selected channels: the total A-weighted level is compared directly with the limit, and the NR fit is performed band by band.
| Function | Description |
|---|---|
| 34 built-in criteria | GB 3096-2008 sound environment classes 0–4b, GB 50118-2010 indoor limits for 7 room types, GB 12348-2008 industrial boundary classes 1–4, GB 12523-2011 construction site boundary, GBZ 2.2 workplace, and NR-15 to NR-85 (15 curves) |
| Day / night | Switch between day and night limits; all results update |
| Eight-channel judgment | All selected channels judged at every refresh, with a result per channel |
| Automatic criterion type | GB criteria use the total A-weighted level; NR criteria switch to the NR curve evaluation automatically |
| Result table | Nine columns: measured A-weighted level, measured NR, criterion type, limit, pass/fail, margin or exceedance in dB, standard, period |
| 1/3-octave spectrum | 30 bands (20 Hz–16 kHz), Z or A weighting (Z locked for NR), with the target NR curve overlaid |
| A-weighted level history | Total A-weighted level of each channel against time (8192 points rolling) with a red limit line |
| Double-click to enlarge | Any chart to full screen for reports and explanation |
| Excel export | The result table for test reports |
| Stay on top and help | Keep the window in front; built-in reference |
The left panel selects channels, the standard and the day or night period.
Compliance monitoring in residential, educational, mixed, industrial and traffic-side areas against GB 3096-2008 classes 0–4b. Select the zone class and period for automatic judgment; the history shows whether exceedance is continuous or intermittent.
Indoor noise acceptance of bedrooms, classrooms, wards and operating theatres, hotel rooms and offices against GB 50118-2010, for completion acceptance and buyer-commissioned tests.
When one boundary faces housing and another an industrial park, different classes apply (GB 12348-2008 classes 1–4). Four boundaries, four points and four limits are judged at the same time — the value of synchronized multi-channel judgment.
The construction site boundary limit (GB 12523-2011) is 70 dB by day and 55 dB at night. Whether night work disturbs residents and how much margin remains is visible in the history with the limit line.
Workplace rounds can identify high-noise tasks. An eight-hour occupational exposure result must be calculated from representative measurements and actual task durations using the applicable occupational method; a single frame or location reading is not that result.
Plant rooms, transformer rooms, lift machine rooms and clean rooms are commonly specified by NR curves in contracts and design codes (for example “plant room NR-45”). NR evaluation fits the Z-weighted octave spectrum to the curve family band by band and gives the measured NR value, avoiding the case of low-frequency rumble where the total level passes but the spectrum does not.
With the built-in example data, the complete sequence — select the standard, judge, read the result, locate the exceeding band — can be demonstrated without field measurement points.
| Item | Question | Engineering meaning |
|---|---|---|
| Total A-weighted level LAeq | Does the overall noise exceed the limit? | Statutory criterion for environmental, boundary, construction and occupational standards |
| Measured NR value | Does the spectral shape meet the NR curve? | Design and acceptance criterion for indoor equipment noise; reveals low-frequency exceedance |
| Limit | How many decibels are allowed for this standard and period? | The limit is visible and the judgment can be checked |
| Pass / fail | The conclusion | Color-coded for non-specialists |
| Margin / exceedance in dB | How far from the limit? | Sets the scale of corrective work: 1 dB and 20 dB call for different solutions |
| 1/3-octave spectrum and NR target | In which bands is the limit exceeded? | Band-by-band comparison points to specific sources (fans, pumps, transformers) |
| A-weighted history and limit line | When is the limit exceeded? | Distinguishes continuous from intermittent exceedance and captures short disturbing events |
The current frame is windowed and transformed by FFT, and the range from 20 Hz to 16 kHz is divided into 30 standard 1/3-octave bands; each band level is the energy sum of its lines:
L_band = 10 · lg(Σ p² / p0²) [dB], p0 = 20 µPa
Empty bands are shown at 0 dB so the curve remains continuous.
rA(f) = 12194² · f⁴ / [(f² + 20.6²) · √((f² + 107.7²)(f² + 737.9²)) · (f² + 12194²)], LA = 20 · lg rA + 2.00
A-weighting models the ear's low sensitivity at low frequencies and is the statutory weighting for environmental and occupational noise.
LAeq = 10 · lg Σ 10^((L_band + A(f)) / 10) [dB(A)]
Pass if LAeq ≤ limit. Margin = limit − LAeq: positive values are margin, negative values the exceedance. Day or night limits apply according to the selected period.
The NR curves are a family of spectral limit curves from NR-0 to NR-100. The module contains the standard limit table for NR-15 to NR-85 in steps of 5 for nine octave bands from 31.5 Hz to 8 kHz, with linear interpolation for any NR value. The evaluation has four steps:
| Step | Operation | Note |
|---|---|---|
| 1 | Combine octave bands | Sum the 1/3-octave spectrum in groups of three to nine Z-weighted octave band levels |
| 2 | Inverse interpolation per band | Find the NR value allowed for each measured band level from the table |
| 3 | Take the highest band | The highest band NR is the measured noise rating — if any band exceeds, the whole spectrum fails |
| 4 | Compare with the target NR | Pass if measured NR ≤ target NR, with the margin or exceedance |
Two details: the NR curves are not parallel across bands, so the target curve is recalculated band by band from the table for the selected rating rather than simply shifted; and the 20 Hz band is extrapolated linearly from the low-frequency trend, while the 12.5 kHz and 16 kHz bands are not defined in the NR system and are excluded.
NR evaluation is based on Z-weighted (linear) octave spectra. Comparing an A-weighted curve with an NR target would push the low-frequency spectrum down and give a false impression of compliance. When an NR criterion is selected, the display is locked to Z-weighting, so the evaluation basis and the chart always agree.
Octave spectra are drawn as steps from lower edge through center to upper edge. The NR target curve is overlaid on the spectrum. The A-weighted history scrolls frame by frame (8192 points), and the red limit line shows the moment of exceedance.
| Standard | Title | Content built in |
|---|---|---|
| GB 3096-2008 | Environmental quality standard for noise | Day and night limits for zone classes 0–4b (6 entries) |
| GB 50118-2010 | Code for design of sound insulation of civil buildings | Indoor limits for bedrooms, classrooms, wards, hotel rooms, operating theatres and offices (7 entries) |
| GB 12348-2008 | Emission standard for industrial enterprises noise at boundary | Day and night limits for boundary classes 1–4 (4 entries) |
| GB 12523-2011 | Emission standard of environment noise for boundary of construction site | 70 dB by day and 55 dB at night (1 entry) |
| GBZ 2.2 | Occupational exposure limits for hazardous agents in the workplace: physical agents | 8 h equivalent level of 85 dB (1 entry) |
| ISO R 1996 (1971) | Noise rating (NR) curves | Octave-band table for NR-15 to NR-85 and the band-wise fitting method (15 curves) |
| IEC 61672-1 / GB/T 3785.1 | Sound level meters, Part 1: specifications | A-weighting transfer function |
| IEC 61260-1 / GB/T 3241 | Octave-band and fractional-octave-band filters | 1/3-octave bands (20 Hz–16 kHz) |
| Capability | Benefit |
|---|---|
| 34 source-reported criteria | Criterion options for comparison; confirm current applicability, measurement basis and averaging period |
| Automatic criterion switching | Selects the source-described GB or NR comparison; formal method validation remains required |
| Color-coded results | Managers and customers can read the result on site |
| Margin in dB | Shows how far from the limit, so corrective work can be sized |
| Automatic NR fit | Band-wise interpolation replaces manual reading, quickly and without errors |
| Eight channels at once | Four boundaries, several floors or many points judged in one measurement |
| Day and night limits follow automatically | No mistakes in day–night monitoring |
| Linked charts | The octave chart shows which band exceeds; the history shows when |
| Limit line on the chart | Intermittent exceedance is visible immediately |
| Excel export | The result table goes straight into test reports |
| Step | Action | Note |
|---|---|---|
| 1 | Select channels | Only enabled channels can be selected (all by default) |
| 2 | Select the criterion | A GB category or an NR rating; with NR, Z-weighting is locked |
| 3 | Select day or night | Limits switch automatically; table and limit line update |
| 4 | Refresh | All selected channels are calculated and judged |
| 5 | Read the result table | Measured value, limit, pass/fail, margin in dB, standard, period |
| 6 | Check the 1/3-octave chart | Confirm exceeding bands against the NR target or the spectral shape |
| 7 | Check the A-weighted history | Confirm when the limit is exceeded against the red line |
| 8 | Export to Excel | Export the result table; use stay on top for side-by-side explanation |
| Situation | Criterion | Limit |
|---|---|---|
| Residential and educational areas | GB 3096-2008 class 1 | 55 dB(A) day / 45 dB(A) night |
| Both sides of main traffic routes | GB 3096-2008 class 4a | 70 dB(A) day / 55 dB(A) night |
| Residential bedroom at night | GB 50118-2010 residential bedroom | Source preset withheld pending current residential-code and measurement-method confirmation |
| Factory boundary next to housing | GB 12348-2008 boundary class 1 | 55 dB(A) day / 45 dB(A) night |
| Construction site boundary | GB 12523-2011 | 70 dB(A) day / 55 dB(A) night |
| Workplace noise | GBZ 2.2 workplace, 8 h | Duration-normalized occupational exposure under the applicable method; not a current-frame criterion |
| Plant rooms and HVAC equipment | NR-XX as specified in the contract | Measured NR ≤ target NR |
Source-display illustration using the GB 3096-2008 class 4a day preset of 70 dB(A). The measurement period, sampling and corrections are not verified, so this is not a formal environmental compliance result.
Read the displayed status and margin, then inspect the bands and history to investigate the source. These readings illustrate the software display only. Confirm the measurement period and the full assessment method before a compliance conclusion or selection of noise-control measures.